Here’s a summary of the Additional Fire Protection Requirements for High Rise and Special Buildings as detailed in Appendix I of the DCPR 20341:
These requirements supplement the general fire protection provisions of the National Building Code of India, allowing the Chief Fire Officer (CFO) to insist on suitable additional measures based on occupancy and height2.
1. Construction 3
- Building Materials:
- Load-bearing elements and elements requiring 1-hour or more fire resistance must be of non-combustible material4.
- Interior finish materials (wall paneling, floor coverings) should not have a flame spread ability exceeding Class I, as per IS:1642,19605.
- Ceiling linings must be non-combustible or plasterboard6.
- Stairways and corridors must not contain combustible materials7.
- Structural Members: Supports and load-bearing walls must have a 3-hour fire resistance rating, while transoms and ceilings require at least 2 hours8.
- Internal Walls and Partitions: Walls separating corridors from other floor areas need at least 1-hour fire resistance9. Openings in such walls are limited to doors or delivery hatches with not less than half-hour fire resistance10.
- Fire Sections (Fire Walls): Sub-dividing walls to prevent fire spread must have a fire resistance rating of at least 2 hours11.
- Facades: Excluding windows and doors, facades must be made of non-combustible materials12. A minimum distance of 0.9m is required between the top of an opening on a lower floor and the sill of the opening on the floor above it, to restrict fire travel between stories13.
2. Staircase Enclosures 14
- Construction: Internal enclosing walls of staircases must be of brick or RCC construction with at least 2-hour fire resistance15.
- Access: All enclosed staircases must be accessed via a ventilated lobby and through self-closing doors with at least half-hour fire resistance, opening in the direction of escape16. These doors require check section door closers17.
- Landing: Staircase floor landings must not form part of a common corridor18.
- Ventilation: Staircase enclosures on external walls must be ventilated at each landing or mid-landing19. A permanent vent (5% of cross-sectional area) at the top and openable sashes (0.5 sq.m minimum area) at each landing level are required on the external wall20.
- Pressure System: If a staircase is in the core of the building and cannot be naturally ventilated at each landing, a positive pressure of 5mm water gauge must be maintained by an electrically operated blower21. This mechanism should operate automatically with fire alarm activation, and manually22.
- Openings: No living space, store, or other fire-risk space should open directly into a staircase23. External exit doors must open directly to open space or a draft lobby24.
- Signs: Exit signs with arrows indicating escape routes must be provided at 1.5m height on walls, painted with fluorescent paint25.
- Basement Access: A single staircase building’s staircase must terminate at the ground floor, with separate access to the basement26. If multiple staircases, one may lead to the basement via a ventilated lobby or cut-off screen wall, staggered at ground floor level27.
3. Lift Enclosures 28
- Construction: Walls enclosing lift shafts must have at least 2-hour fire resistance29. Shafts need permanent vents at the top (min 1800 sq. mm clear area)30.
- Landing Doors: Landing doors must open into ventilated or pressurized corridors/lobbies and have at least 1-hour fire resistance31.
- Lift Banks: No more than four lifts in one bank32. Fire lift shaft must be separated by a 2-hour fire-resisting wall33. Lift car doors must have 1-hour fire resistance34.
- Pressure System: If lift shaft and lobby are in the building core, a positive pressure (2.5-3mm water gauge in lobby, 5mm in shaft) must be maintained35. This system operates automatically with detectors and alarms, and manually36.
- Smoke Stop Door: Exits from lift lobbies (in core) must be through a self-closing smoke stop door with half-hour fire resistance37.
- Lift Machine Room: Must be separate, with no other machinery38.
- Basement Communication: Lifts normally don’t communicate with basements39. One lift may, provided the basement lobby is pressurized and separated by a 2-hour fire-resisting, smoke-actuated door40.
4. External Windows 41
- Area of openable external windows on a floor must be at least 2.5% of the floor area42. Locks must be budget-lock type (openable with a fireman’s axe)43.
5. Fire Lifts 44
- One or more lifts must be designed for exclusive use of fire services during emergencies, directly accessible to every floor45.
- Specifications: Min 1.4 sq.m floor area, min 1.12m dimension, 545 kg (8 persons) capacity, automatic closing doors46.
- Alternate Supply: Must have alternate electric supply from a generator, with cables in a fire-safe route47.
- Operation: Simple toggle or two-button switch at entrance level makes landing call-points inoperative; lift operates on car control only48.
- Signage: “FIRE LIFT” displayed conspicuously in fluorescent paint on landing doors49.
- Doors: Solid doors with at least 1-hour fire resistance; collapsible gates not permitted50.
- Speed: Must reach top floor from ground in one minute51.
6. Basements 52
- Ventilation: Each basement must be separately ventilated, with vents (aggregate 2.5% of floor area) or a system of air inlets at floor level and smoke outlets at ceiling level53. Mechanical extractors for smoke venting are required for lower basement levels54.
- Staircases: Basement staircases must be enclosed (at least 2-hour fire resistance), situated at the periphery, entered from open air at ground level, and communicate via a lobby with 1-hour fire-resisting self-closing doors55.
- Kitchens: Kitchens using gas fuel are not permitted in basements56.
7. Floor Space Division (Fire Sections) 57
- Floor space division on floors and in basements must comply with NBC provisions58.
8. Service Ducts 59
- Enclosed by walls with at least 2-hour fire resistance; inspection/access doors also 2-hour fire resistance60.
- If cross-sectional area > 1 sq.m, sealed where it passes a floor with non-combustible material61.
- Permanent vent at top of service shaft (min 460 sq.cm or 6.25 sq.cm for each 900 sq.cm of shaft area)62.
9. Refuse Chutes and Refuse Chambers 63
- Hoppers under chutes in well-ventilated positions, chutes extending above roof with 2-hour non-combustible enclosure64.
- Inspection panels and hopper openings with 1-hour fire-resisting metal doors/covers65.
- Refuse chutes not in staircase walls or AC shafts66.
- Refuse chambers with 2-hour fire-resisting, non-combustible, impervious walls/floors/roofs, located safely from exits67.
10. Building Services 68
- Electrical Services: Cables in separate sealed ducts, separate circuits for essential services (pumps, lifts, lighting, pressurizing fans), fire-rated inspection panel doors, metal conduits for wiring in shafts/false ceilings69.
- Town Gas/L.P. Gas Supply Pipes: Run in exclusive shafts on external walls, away from staircases, with no inter-connection to floors70.
- Staircase and Corridor Lightings: Separate circuits, independently connected, operable from ground floor, connected to alternate supply71. Emergency lights required72.
- Alternate Source of Electric Supply: Stand-by electric generator for essential services (lighting, fire lifts, fire pump, pressurization fans, smoke extraction/damper systems) in case of normal supply failure73.
- Transformer: If in basement, in first basement in a separate 4-hour fire-resisting room at periphery, protected by CO2 or BCF system74. Direct access from outside preferred75. If at ground floor, cut-off by 4-hour fire-resisting walls76. Not on upper floors except stilt/podium (if dry type)77.
- Air-conditioning: Escape routes not to be used as return air passages78. Ducting of substantial gauge metal, sealed where passing through fire-walls/floors79. Metallic ducts preferred for return air80. Non-combustible insulation81. Fire dampers where ducts pass through fire walls, and at air handling unit inlets82. Air handling units preferably separate for each floor83. Non-combustible air filters84.
- Boiler Room: Must conform to Indian Boilers Act85. Not in lower basement86. In 4-hour fire-resisting room at periphery, away from escape routes87. Foam inlets on external walls for fire services88.
11. Provision of First Aid and Fire-fighting Appliances 89
- First-aid firefighting equipment on all floors (including basements, lift rooms) as per IS: 2217-196390.
- Appliances distributed as per IS: 2190-197191.
12. Fixed Fire-Fighting Installations 92
- Wet riser, wet riser-cum-down comer, automatic sprinkler, high-pressure water spray, or foam generating system93.
- Wet Riser/Riser-cum-Down Comers: Capacity of water storage tanks and fire pumps as specified in Table (e.g., 50,000 to 3,00,000 litres underground static tank, 20,000 to 50,000 litres terrace tank depending on building height/type)94. Exclusive for firefighting95.
- Static Water Storage Tank: Underground static tank (capacity specified for building) with replenishment arrangements96. Must be accessible to fire engines97.
- Automatic Sprinklers: Installed as per NBC98.
- High Pressure Water Spray (emulsifying): For indoor transformers in basement99.
- Foam Generating System: For boiler rooms with furnace oil storage100.
- Carbon-dioxide (Co2) Fire Extinguishing System: For premises where water/foam cannot be used101.
13. Fire Alarm System 102
- Manually-Operated Electrical Fire Alarm System: For special buildings >15m height and Business/Industrial buildings >32m height103. Call boxes on each floor (accessible within 30m travel distance)104.
- Automatic Fire Alarm System: For all other buildings >32m height (in addition to manual system)105. Detectors conform to IS Specification106.
14. Lightning Protection of Buildings 107
- Lightning protection systems must conform to Part III, National Building Code of India108.
15. Control Room 109
- For buildings mentioned in fire alarm section (except residential), a control room on the entrance floor with communication system to all floors, firefighting equipment details, and indicator boards110. Manned 24/7111.
16. Fire Drills and Fire Orders 112
- Fire notices/orders must be prepared and displayed, and occupants familiarized with emergency actions113.
17. Location of Refuge Area 114
- Location: Preferably within building line at floor level, facing access road/wider open space115. Cantilevered refuge area permissible at staircase mid-landing only116. All other refuge areas within building line117.
- Frequency: First refuge area at 24m or 1st habitable floor (whichever is higher) for buildings >32m height. Thereafter, at every 7th habitable floor118.
- Size: 4% of habitable floor area it serves, free of FSI. Can be up to 4.25% with Commissioner’s permission119.
- Alternate (up to 70m height): RCC cantilever projections at alternate mid-landing levels of staircase (min 3.0m width, min 10.0 sq.m residential / 15 sq.m non-residential) free of FSI120.
- Up to 32m height: Terrace floor treated as refuge area121.
- Use: Exclusively for temporary shelter for occupants and use by Fire Brigade122. Must be maintained clean and free of encumbrances123.
- Facilities: Adequate emergency lighting, toilet, drinking water124.
18. Glass Façade 125
- All buildings with glass façade must comply with fire safety requirements as per Model Building Bye Laws/NBC126.
